ELECTRICAL DATA
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
1.Rated Voltage |
12KV |
2.Rated Current |
630/1250A |
3.Rated Frequency |
50Hz |
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
5.Rated lightring Impulse Withstand Voltage |
75KV |
6. Rated short-circuit breaking current |
25KA |
7. Rated short-circuit making current(peak) |
63KA |
8.Rated operations of short-circuit breaking current interruption |
30times |
9.Rated single capacitor bank breaking current interruption |
630A |
10.Rated Short-time Withstand current |
25KA |
11.Rated peak withstand current |
63KA |
12. Rated Duration of Short-circuit |
4s |
13. Mechanical Life |
20000times |
14.Contact closing force due to bellows and atmosphere |
120±50N |
15.Counterforce at rated contact stroke |
190±60N |
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
17. Shelf Life |
20Years |
18. Contact Erosion Limit |
3mm |
19.Weight of moving parts |
≤1.5kg |
MECHANICAL REQUIREMENTS(REF. VCB) |
|
1. Rated Contact Stroke |
10±1mm |
2.Opening Speed(average) |
1.0±0.25m/Sec |
3.Closing Speed(average) |
0.65±0.15m/Sec |
4.Added contact force |
2000±100N |
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
Main Technical Specification |
Unit |
Specification |
Rated contact stroke |
mm |
9±1 |
Average opening speed |
m/s |
1.0±0.25 |
Average closing speed |
m/s |
0.65±0.15 |
Added contact force |
N |
900/1300/1600±100 |
Contact bouncing duration at closing operation |
ms |
≤2 |
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:
Related Product Guide:
Things Your Electrician Wishes You Knew | Circuit Breaker Parts
BMW’s iX3 is the company’s first normal-looking all-electric car | 25 Amp Circuit Breaker
It truly is our responsibility to fulfill your requirements and successfully provide you. Your fulfillment is our best reward. We're seeking forward in your check out for joint development for Bottom price Light Switching Latching Relay - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: Ukraine , Maldives , Denver , Based on experienced engineers, all orders for drawing-based or sample-based processing are welcomed. We have now won a good reputation for outstanding customer service among our overseas customers. We will continue to try the best to supply you good quality products and solutions and the best service. We've been looking forward to serving you.
By Julie from Danish - 2016.01.28 18:53
We have been appreciated the Chinese manufacturing, this time also did not let us disappoint,good job!
By Heather from Pakistan - 2015.06.18 19:26