ELECTRICAL DATA
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
1.Rated Voltage |
12KV |
2.Rated Current |
630/1250A |
3.Rated Frequency |
50Hz |
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
5.Rated lightring Impulse Withstand Voltage |
75KV |
6. Rated short-circuit breaking current |
25KA |
7. Rated short-circuit making current(peak) |
63KA |
8.Rated operations of short-circuit breaking current interruption |
30times |
9.Rated single capacitor bank breaking current interruption |
630A |
10.Rated Short-time Withstand current |
25KA |
11.Rated peak withstand current |
63KA |
12. Rated Duration of Short-circuit |
4s |
13. Mechanical Life |
20000times |
14.Contact closing force due to bellows and atmosphere |
120±50N |
15.Counterforce at rated contact stroke |
190±60N |
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
17. Shelf Life |
20Years |
18. Contact Erosion Limit |
3mm |
19.Weight of moving parts |
≤1.5kg |
MECHANICAL REQUIREMENTS(REF. VCB) |
|
1. Rated Contact Stroke |
10±1mm |
2.Opening Speed(average) |
1.0±0.25m/Sec |
3.Closing Speed(average) |
0.65±0.15m/Sec |
4.Added contact force |
2000±100N |
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
Main Technical Specification |
Unit |
Specification |
Rated contact stroke |
mm |
9±1 |
Average opening speed |
m/s |
1.0±0.25 |
Average closing speed |
m/s |
0.65±0.15 |
Added contact force |
N |
900/1300/1600±100 |
Contact bouncing duration at closing operation |
ms |
≤2 |
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:



Related Product Guide:
Yes, the Samsung Galaxy S9 has a headphone jack | 25 Amp Circuit Breaker
Here’s a sure red flag the home contractor you’re considering is untrustworthy | Lrd12 Overload Relay
With reliable good quality system, great standing and perfect consumer support, the series of products and solutions produced by our organization are exported to quite a few countries and regions for China wholesale Telemecanique Dc Contactor - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: Armenia , Uruguay , belarus , Providing Quality Products, Excellent Service, Competitive Prices and Prompt Delivery. Our products are selling well both in domestic and foreign markets. Our company is trying to be one important suppliers in China.

The company leader recept us warmly, through a meticulous and thorough discussion, we signed a purchase order. Hope to cooperate smoothly

-
OEM/ODM Manufacturer Hot Saile Ac Contactor - ...
-
Renewable Design for Digital Power Timer - Nof...
-
China Supplier Definite Contactor - LC1F Conta...
-
Super Purchasing for 100a Mzj-100 Dc Reversing ...
-
Good User Reputation for Coil For Contactor - ...
-
Top Suppliers Latching Contactors Relay - Moto...