Factory directly supply Contactor Siemens 3rt1015 - Vacuum Interruption VI 12KV WL-39418 – Simply Buy Detail:
A perfect fit for many applications
Load break switches
• Motor contactors
• Circuit breakers
• Reclosers
• Transportation breakers
• Ring main / pad mount units
• Specialized DC applications
• Generator breakers
• Distribution circuit breakers
• Medium voltage switchgear
ELECTRICAL DATA
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
1.Rated Voltage |
12KV |
2.Rated Current |
630/1250A |
3.Rated Frequency |
50Hz |
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
5.Rated lightring Impulse Withstand Voltage |
75KV |
6. Rated short-circuit breaking current |
25KA |
7. Rated short-circuit making current(peak) |
63KA |
8.Rated operations of short-circuit breaking current interruption |
30times |
9.Rated single capacitor bank breaking current interruption |
630A |
10.Rated Short-time Withstand current |
25KA |
11.Rated peak withstand current |
63KA |
12. Rated Duration of Short-circuit |
4s |
13. Mechanical Life |
20000times |
14.Contact closing force due to bellows and atmosphere |
120±50N |
15.Counterforce at rated contact stroke |
190±60N |
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
17. Shelf Life |
20Years |
18. Contact Erosion Limit |
3mm |
19.Weight of moving parts |
≤1.5kg |
MECHANICAL REQUIREMENTS(REF. VCB) |
|
1. Rated Contact Stroke |
10±1mm |
2.Opening Speed(average) |
1.0±0.25m/Sec |
3.Closing Speed(average) |
0.65±0.15m/Sec |
4.Added contact force |
2000±100N |
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
Main Technical Specification |
Unit |
Specification |
Rated contact stroke |
mm |
9±1 |
Average opening speed |
m/s |
1.0±0.25 |
Average closing speed |
m/s |
0.65±0.15 |
Added contact force |
N |
900/1300/1600±100 |
Contact bouncing duration at closing operation |
ms |
≤2 |
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:



Related Product Guide:
Is my appliance compatible with the Amazon Smart Plug? | Lrd12 Overload Relay
More people watched the Logan Paul vs. KSI fight on Twitch than on YouTube | 220v Contactor Relay
We not only will try our greatest to offer superb companies to just about every buyer, but also are ready to receive any suggestion offered by our shoppers for Factory directly supply Contactor Siemens 3rt1015 - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: Rwanda , Bolivia , France , Our solutions have national accreditation standards for experienced, premium quality goods, affordable value, was welcomed by people around the globe. Our products will continue to increase in the order and look forward to cooperation with you, Truly must any of people goods be of interest to you, make sure you letus know. We're likely to be delighted to give you a quotation up on receipt of one's in depth specs.

It can be said that this is a best producer we encountered in China in this industry, we feel lucky to work with so excellent manufacturer.