Factory wholesale Telemechanic Ac Contactor - LC1-K TeSys K mini contactor – Simply Buy Detail:
Type |
Rated working current A(380V) | 220V |
AC-3 use group control power (kW) 380V~415V 440~500V |
660V | Contact data(1) | |||
LC1-K06 |
6 |
1.5 |
2.2 |
3 |
3 |
3P+NO 3P+NC | ||
LC1-K09 |
9 |
2.2 |
4 |
4 |
4 |
3P+NO 3P+NC | ||
LC1-K12 |
12 |
3 |
3 |
5 |
5 |
3P+NO 3P+NC |
Specifications LC1-K06 LC1-K09 LC1-K12 | |||||
Use group under AC-3 |
6 |
9 |
12 |
||
Rated working current(le)A |
5 |
7.5 |
10 |
||
Conventional thermal current(lth)A |
16 |
20 |
20 |
||
Rated working voltage(Ue)V |
380 660 |
||||
Rated insullation voltage(Ui)V |
690 |
||||
AC-3(6le le) | Electrical life(time) |
0.5×106 |
|||
Operation frequency h-1 |
1200 |
||||
AC-3(6le le) | Electrical life(time) |
10×104 |
|||
Operation frequency h-1 |
300 |
||||
Mecnical life Auxiliary contact | Conventional thermal current |
3×106 6A |
|||
Electrical life(time) | AC-15(360VA) |
0.5×106 |
|||
DC-13(33W) | |||||
Coil specifications | Rated control voltage(Us) | AC: 12, 24, 45, 110, 220, 380 | |||
DC: 12, 24, 45, 110, 220 | |||||
Pick-up voltage | AC: 0.85~1.1Us DC: 0.85~1.1Us | ||||
Resleasing voltage | AC: 0.2~0.75Us DC: 0.2~0.75Us | ||||
Coil power VA | Pick-up |
40 |
|||
Fotain |
4 |
||||
Consumption |
1.2W |
||||
Pick-up time |
6~18ms |
||||
Releasing timePower factor |
5~23ms Making 0.8 Breaking 0.3 |
AC operating coils
Maximum Horsepower Ratings | Maximum Current | Type of Connection | Auxiliary Contacts | Catalog Number |
|||||||
1 Ø | 3 Ø | Inductive AC3 Amperes |
Resistive AC1 Amperes |
||||||||
115 V hp | 230 V hp | 200 V hp | 230 V hp | 460 V hp | 575 V hp | N.O. | N.C. | ||||
0.5 | 1.5 | 1.5 | 1.5 | 3 | 3 | 6 | 15 | Screw-clamp | 1— | —1 | LC1K0610 LC1K0601 |
0.5 | 1.5 | 2 | 3 | 5 | 5 | 9 | 20 | Screw-clamp | 1— | —1 | LC1K0910 LC1K0901 |
0.5 | 1.5 | 3 | 3 | 7.5 | 10 | 12 | 20 | Screw-clamp | 1— | —1 | LC1K1210 LC1K1201 |
Coil voltage codes for AC contactors
Volts AC 50/60 Hz | 12 |
24 |
42 | 48 | 110 | 120 | 127 | 200/ 208 |
220/ 230 |
230 | 230/ 240 |
277 | 380/ 400 |
400/ 415 |
440 | 480 |
Code | J7 |
B7 |
D7 | E7 | F7 | G7 | FC7 | L7 | M7 | P7 | U7 | UE7 | Q7 | N7 | R7 | T7 |
DC operating coils
0.5 | 1.5 | 1.5 | 1.5 | 3 | 3 | 6 | 15 | Screw-clamp | 1— | —1 | LP1K0610 abLP1K0601 ab |
0.5 | 1.5 | 2 | 3 | 5 | 5 | 9 | 20 | Screw-clamp | 1— | —1 | LP1K0910 abLP1K0901 ab |
0.5 | 1.5 | 3 | 3 | 7.5 | 10 | 12 | 20 | Screw-clamp | 1— | —1 | LP1K1210 abLP1K1201 ab |
Overload relays for 3-Pole contactors with screw-clamp terminals
Class 10, Relay setting range–A | Catalog Number | |
0.1 to 0.16 | LR2K0301 | LR2K overload relays:
|
0.16 to 0.23 | LR2K0302 | |
0.23 to 0.36 | LR2K0303 | |
0.36 to 0.54 | LR2K0304 | |
0.54 to 0.8 | LR2K0305 | |
0.8 to 1.2 | LR2K0306 | |
1.2 to 1.8 | LR2K0307 | |
1.8 to 2.6 | LR2K0308 | |
2.6 to 3.7 | LR2K0310 | |
3.8 to 5.5 | LR2K0312 | |
5.5 to 8 | LR2K0314 | |
8 to 11.5 | LR2K0316 | |
10 to 14 | LR2K0321 |
Product detail pictures:
Related Product Guide:
Could A Fire Have Caused The Loss Of MH370? | Circuit Breaker Parts
Hot circuit breakers and dimmer switches | 25 Amp Circuit Breaker
We believe in: Innovation is our soul and spirit. Quality is our life. Customer need is our God for Factory wholesale Telemechanic Ac Contactor - LC1-K TeSys K mini contactor – Simply Buy, The product will supply to all over the world, such as: South Korea , Sacramento , Georgia , The design, processing, purchasing, inspection, storage, assembling process are all in scientific and effective documentary process , increasing usage level and reliability of our brand deeply, which makes us become superior supplier of the four major product categories shell castings domestically and obtained the customer's trust well.
By Maureen from Bangkok - 2016.04.08 14:55
Adhering to the business principle of mutual benefits, we have a happy and successful transaction, we think we will be the best business partner.
By Sara from Suriname - 2016.08.18 11:04