New Fashion Design for Original Contactor - Vacuum Interruption VI 12KV WL-39418 – Simply Buy Detail:
A perfect fit for many applications
Load break switches
• Motor contactors
• Circuit breakers
• Reclosers
• Transportation breakers
• Ring main / pad mount units
• Specialized DC applications
• Generator breakers
• Distribution circuit breakers
• Medium voltage switchgear
ELECTRICAL DATA
ELECTRICAL RATINGS(3PHASE) SYMMETRICAL BASIS |
|
1.Rated Voltage |
12KV |
2.Rated Current |
630/1250A |
3.Rated Frequency |
50Hz |
4.Rated Short-time Power Frequency Withstand Voltage(1min) |
42KV |
5.Rated lightring Impulse Withstand Voltage |
75KV |
6. Rated short-circuit breaking current |
25KA |
7. Rated short-circuit making current(peak) |
63KA |
8.Rated operations of short-circuit breaking current interruption |
30times |
9.Rated single capacitor bank breaking current interruption |
630A |
10.Rated Short-time Withstand current |
25KA |
11.Rated peak withstand current |
63KA |
12. Rated Duration of Short-circuit |
4s |
13. Mechanical Life |
20000times |
14.Contact closing force due to bellows and atmosphere |
120±50N |
15.Counterforce at rated contact stroke |
190±60N |
16. Circuit Resistance at Rated Contact Froce Atmosphere Force |
≤20Micro ohms |
17. Shelf Life |
20Years |
18. Contact Erosion Limit |
3mm |
19.Weight of moving parts |
≤1.5kg |
MECHANICAL REQUIREMENTS(REF. VCB) |
|
1. Rated Contact Stroke |
10±1mm |
2.Opening Speed(average) |
1.0±0.25m/Sec |
3.Closing Speed(average) |
0.65±0.15m/Sec |
4.Added contact force |
2000±100N |
5. Maximum Contact Bounse Duration at closing operation |
≤2ms |
6. Contact Bouncing Bank Amplitude of Opeing Operation |
≤2mm |
7.Three-pole simultaneity |
≤1ms |
Mechanical Data Required For Matched Vacuum Switchgear
Main Technical Specification |
Unit |
Specification |
Rated contact stroke |
mm |
9±1 |
Average opening speed |
m/s |
1.0±0.25 |
Average closing speed |
m/s |
0.65±0.15 |
Added contact force |
N |
900/1300/1600±100 |
Contact bouncing duration at closing operation |
ms |
≤2 |
Contact bouncing bank amplitude of opening operation |
mm |
≤2 |
Three-pole simultaneity |
ms |
≤1 |
Product detail pictures:
Related Product Guide:
Firefox Monitor will let you know if your data has been stolen | 220v Contactor Relay
Motor Nameplate Current vs. NEC Full Load Current Values | National Electrical Code | 25 Amp Circuit Breaker
Generally customer-oriented, and it's our ultimate goal for being not only the most trusted, trustable and honest provider, but also the partner for our customers for New Fashion Design for Original Contactor - Vacuum Interruption VI 12KV WL-39418 – Simply Buy, The product will supply to all over the world, such as: Swansea , Turkey , Juventus , Our expert engineering team will generally be prepared to serve you for consultation and feedback. We are able to also offer you with free of charge samples to meet your requirements. Best efforts will likely be produced to provide you the best service and merchandise. When you are keen on our business and products, please speak to us by sending us emails or call us quickly. In an effort to know our products and company extra, you may come to our factory to view it. We will generally welcome guests from all over the world to our business to create business relations with us. Please feel cost-free to speak to us for small business and we believe we'll share the best trading experience with all our merchants.
By Steven from Liverpool - 2016.03.08 14:45
The company leader recept us warmly, through a meticulous and thorough discussion, we signed a purchase order. Hope to cooperate smoothly
By Sabrina from Afghanistan - 2015.11.22 12:28